All Categories

Zeta 4 Zone Conventional Fire Alarm Panel

Art.Nr.:

BCFQ-8712

Call for Price

Short Details:

Features:

– Access via password – removes problem of lost keys

– One man test facility

– Disablement facility for zones & sounders

– Space for up to 3Ah batteries

– Sounder delay option

– 4 sounder circuits (IN4, IN6 & IN8)

– Sounder circuits 3 and/or 4 can be configured as Aux 24V supplies

– Meets all requirements of latest EN54 part 2 and part4

Description

Brand : ZETA

Model : Infinity 8 – IN4

Country of Origin: UK

 

Description :   

The Infinity 8 control panel is housed in the most attractive, modern designed, flame retardant ABS enclosure, utilizing a switch mode power supply. It has a fully removable front cover which improves ease of access for cable installations.

 

Technical Specifications:    

 

 ModelIN1IN2IN4IN6IN8
Part No37-65037-65137-65237-65337-654
Mains Voltage230V AC +10% / -15% @ 50/60 Hz
System Voltage24V DC (Nominal)
Zone Voltage21V DC (Nominal)
Sounder Alarm Output2 x 150mA @ 24V DC4 x 150mA @ 24V DC
Fire Relay1 x Volt Free Relay, SELV @ 1A Max
Fault Relay1 x Volt Free Relay, SELV @ 1A Max
Zone Capacity32 devices per zone
Remote sounder operationVia N/O contact connected to Class Change
Sounder Activation Delay0 to 10 minutes in 1 minute increments
Zone End of line1N4002 Diode (Cathode Stripe to Zone +ve)
Sounder End of Line10K resistor
Charger Voltage27.6V
Battery cut offBattery voltage less than 20V
Battery Internal Resistance limit0.9 ohm
Enclosure size371 x 302 x 93 (mm)
Weight3 kg (Excluding Batteries)
Maximum battery space2 x 3.4 Ah, 12 Vdc sealed lead acid